(42.45 € HT)
G10 Inhibitor - 1L can FNL
G10 INHIBITOR is an anti-corrosion and anti-scaling product designed to protect closed central heating circuits filled with non-softened water. It can be used to protect a new installation or after the de-silting treatment of an existing installation.
Can be applied to a new installation or after de-silting an existing one - Protects against corrosion, prevents sludge formation and eliminates boiler noise - Suitable for all metals (steel, copper, brass, cast iron, aluminium) as well as for plastic pipes used in underfloor heating systems (PER, PEX, PB, PP, PVC) - Contains a biocide that prevents bacterial contamination - Compatible with the other products in the GEB HVAC range.
Orange liquid
Aromatic Odor
Compatible with most hardware.
Does not damage radiator and boiler nipple seals
"Use biocides with care. Read the label and product information before use.
- Turn off the boiler.
- Drain the system by a few litres.
- Fill the heating circuit by incorporating the G10 INHIBITOR at the level of the drain head of a radiator, in the upper part of the installation. The dose is 1 litre for a 100 litre installation.
- Pressurize the system and then turn on the circulation pump for at least 30 minutes to homogenize the solution. Leave the product in the system, do not drain.
- In the event of a major water top-up, it is imperative to add G10 INHIBITOR in order to restore the 1%.
- Product lifetime: 5 years.
To know the exact volume of your installation, think of taking these readings:
- Before the first filling of a new installation or following a de-silting, take the water meter reading (V1)
- Performing the filling
- Water meter reading (V2)
The volume of your installation is obtained by the difference Ve = V2 - V1